Status
Last reviewed 3 September 2026.
✅ Settled
|
|
| The retrofit boundary |
Eight connectors on the Housing's front panel. No field wiring disturbed, no field wire re-terminated |
| Servo control mode |
Analog velocity. Proved from the drawing, not the drive panel — the pulse inputs are not wired and there are not enough spare pins or conductors to carry them. The drive settings stay exactly as they are |
| Homing |
The drives are not self-homing; the controller homes them, switch plus encoder index. Reproduces in LinuxCNC with no extra wiring |
| Mesa hardware |
7I76EU + 7I77U + 7I84U, all bought. 96 inputs and 48 outputs against 41 and 41 required |
| The I/O map |
All 82 points: address → module terminal → wire → cabinet terminal → connector pin → device |
| The Housing connectors |
Every one, pin by pin, with part numbers |
| Locating-stop interlock |
Spindle inhibited until the stops are commanded down and a dwell has elapsed. No sensors, by decision |
🔨 In progress
|
|
| Control logic |
Every function mapped to its I/O and to the LinuxCNC mechanism. Next: mine the original PLC source function by function |
| Simulation config |
Written, not yet run |
| Connector order |
Panel-mount D-subs, ribbon headers and cable specified. Buying |
🔴 Open — needs the machine running
These three can be answered in a single session and all need the original controller still in place. They cannot be answered after strip-out.
|
|
| Ribbon way ↔ I/O address |
Which of the 26 ways carries which point. Likely ways 1–24 in order with 25–26 the module supply, but unproven. Test at four ways per ribbon, not all 24 |
| Ribbon logic voltage and polarity |
Sets the Mesa field-power domains |
| Where the I/O modules get logic power |
Two spare ways on a 26-way suggests the ribbon carries it |
🔴 Open — other
|
|
IF.21: index sensor or change piston? |
The symbolic map and the connector schedule disagree about the same wire. Settle before writing the ATC — if it is really a spindle index, tool-change orientation is achievable; if not, it is not |
| Drive scaling parameters |
The PG divider ratio and speed reference gain still have to be read off the drive panels. Do not assume catalogue defaults |
| The rope switch identity |
A dashed device in the under-table box is the strong candidate. Confirm physically |
| Should a raised stop also inhibit traverse? |
Not just the spindle. One more logic block if wanted |
What is deliberately not being done
|
|
| Sensors on the locating stops |
Decided against. The interlock proves the command was given and time allowed, not that the pin moved — the same exposure the machine has today |
| Cable restraint inside the Housing |
Not needed for short internal runs |
| Replacing the safety chain with software |
The enable rail, the drive-OK relays, the overtravel path and the Z brake stay hardwired. Mesa only monitors |
| Touching the drives |
They work, they are correctly configured, and their looms are professionally made assemblies |